Cross-Sec (Sq.mm) | Approximate No.of Wires x Single Wire Ø (mm) | Radial thickness of sheathing (mm) | Outer Diameter min ~ max (mm) | Max Resistance @20°C (ohm/km) | Current Rating At a Max Duty Cycle | Approx.Awg.No | |||
---|---|---|---|---|---|---|---|---|---|
Permanent 100% (Amps) | 85% (Amps) | 60% (Amps) | 30% (Amps) | ||||||
1x35 | 969 x 0.2 | 2.0 | 11.1 ~ 13.1 | 0.570 | 200 | 230 | 270 | 380 | 2 |
1x50 | 1326 x 0.2 | 2.2 | 13.0 ~ 15.0 | 0.410 | 270 | 300 | 350 | 470 | 1 |
1x70 | 1938 x 0.2 | 2.4 | 15.2 ~ 17.2 | 0.290 | 350 | 370 | 440 | 600 | 2/0 |
1x95 | 2550 x 0.2 | 2.6 | 17.9 ~ 19.9 | 0.220 | 420 | 450 | 530 | 740 | 3/0 |
1x120 | 1406 x 0.3 | 2.8 | 19.2 ~ 22.2 | 0.190 | 480 | 515 | 380 | 780 | 4/0 |
Nominal crosssectional area ofconductor | Maximum conductorresistance at 20° | Maximum diameter of wire of conductor | Strands | Mean overalldiameter | Thickness ofcovering | Average cableweight | Standard packaging |
---|---|---|---|---|---|---|---|
mm | Ohm/Km | mm | N° | mm | mm | Gr/mt. | Mt. |
35 | 0.640 | 0.31 | 7 | 11.6 | 2.0 | 345 | 100 |
50 | 0.450 | 0.31 | 7 | 13.1 | 2.3 | 475 | 100 |
70 | 0.325 | 0.31 | 7 | 15.1 | 2.4 | 634 | 100 |
95 | 0.206 | 0.31 | 7 | 18.2 | 2.8 | 1000 | 50 |
120 | 0.161 | 0.31 | 7 | 20.4 | 3.0 | 1240 | 50 |